GCL-GCXOPENOPENCLOSESTOPCALRUN SCROLLSCROLLSETCLEARSetting Mid-Stop LimitMID-STOP SETFigure 14CALRUNSCROLSETCLEARRUNCLOSECALRUNCALRUNALSETCLEARSCROLLThe operator includes a programmable Mid-Stop. This feature allowsthe operator to stop at a user selectable point when opening. It is usedwhen operating very tall doors that only open to their full heightoccasionally. The Mid-Stop does not effect the operator when closing. Tooperate door to full open position from mid-stop, press open button again.NOTE: Setting of the MID-STOP should only be performed AFTER TravelLimit and Max Run Timer settings have been made.1) Press CAL/RUN to enter calibration mode.2) Press the CLOSE to close the door to the down limit.3) Press SCROLL until display reads “MID-STOP >CLR” Figure 14NOTE: If the display reads MID-STOP > SET at this point, first clearMID-STOP as described below then repeat steps 1-3 and continue.4) Press the OPEN to open the door to desired mid-stop height.5) Press SET/CLEAR until the display reads ”MID-STOP > SET”6) Press CAL/RUN to return to run mode.To CLEAR the Limit1) Press CAL/RUN to enter calibration mode.3) Press SCROLL until display reads “MID-STOP >SET”5) Press SET/CLEAR until the display reads ”MID-STOP > CLR”8) Press CAL/RUN to return to run mode.6.6www.geniecompany.com 08-12Counter Door Operator