ー 127 ーOperating Instructions Intelligent Controller162Configuring the system SettingLinked control of air conditioning unitsBy setting conditions for input points and output points, you can perform linked control of air conditioningunits (indoor units and outdoor units).For example, you can make a setting so that all indoor units stop operating at the same time (output point)in response to a fire alarm going off (input point).4 Select the input point border (4-1) andtouch [Set] (4-2).z The “Input point settings” dialogue is displayed.4- 14- 25 Select the input target from the list.z Input targets include air conditioner alarms, digital input/output devices, indoor units (individual and control groups).5Continued on next page1 Touch [System Settings] in “Settings”.z The “System settings” screen is displayed.12 Touch [Event control].z The “Event control” screen is displayed.23 Select an event name.z Use to select the name to register the event.z You can change the event names. (→ “Changing an eventname” (P.167))3163Configuring the system Setting6 Setting the input conditions.z The items you can set depend on the input target selected.6 When air conditioning unit alarm batch is selectedItem ExplanationMltAlrms Select either “ON” or “OFF”.y “ON” indicates that an error alarm has beentransmitted.y “OFF” indicates that a unit has recovered from anerror. When a digital input/output device is selectedDigitalInput Select either “ON” or “OFF”.y “ON” is displayed when digital input signals are on.y “OFF” is displayed when digital input signals are off. When an indoor unit has been selectedI/DUnt* Ope. Select either “ON” or “OFF”.y “ON” is displayed when operation of theindoor units has been started.y “OFF” is displayed when operation of theindoor units is stopped.Alarm Select either “ON” or “OFF”.y “ON” indicates that an error alarm hasbeen transmitted.y “OFF” indicates that a unit has recoveredfrom an error.Room T Set the room temperature. The touchscreennumeric keypad appears when you touchthe text box.Select either “min.” or “max.”.y “min.” indicates when the temperature isabove the set temperature.y “max.” indicates when the temperature isbelow the set temperature.* Set one of the condition items on the right.7 Touch [Register].z The “Input point settings” dialogue closes.z To cancel the settings, touch [Cancel].78 Select the output point border (8-1) andtouch [Set] (8-2).z The “Output point settings” dialogue is displayed.8- 18- 29 Select the output target from the list.z Output targets include digital input/output devices, indoorunits (all at once, individual, and control groups).9Continued on next pageLinked control of air conditioning units