7Itemcode Item Setting dataNo. Description No. Description No. DescriptionType0000 1-Way Cassette (D1) 0001 4-Way Cassette(U1, Y1) 0002 2-Way Cassette (L1)0003 1-Way Cassette (D1) 0005Low Silhouette Ducted/Slim Low Static Ducted(F1, M1)0006 Ducted (E1)0007 Ceiling (T1) 0008 Wall mounted (K1) 0010 Floor Standing (P1)0011 Concealed FloorStanding (R1)Indoor unitcapacity0001 22 (Type 7) 0003 28 (Type 9) 0005 36 (Type 12)0007 45 (Type 16) 0009 56 (Type 18) 0011 71 (Type 25)For FR25 and FMR250012 80 (Type 25)(Except FR25, FMR25) 0015 112 (Type 36) 0017 140 (Type 48)0018 160 (Type 60) 0021 224 (Type 70) 0023 280 (Type 96)Systemaddress0001 Unit No. 10002 Unit No. 20003 Unit No. 30030 Unit No. 300099 Not setIndoor unitaddress0001 Unit No. 10002 Unit No. 20003 Unit No. 30064 Unit No. 640099 Not setGroup controladdress0000 Individual (1:1 = Indoor unit with no group wiring)0001 Main unit (One of the group-control indoor units)0002 Sub unit (All group-control indoor units except for main unit)0099 Not setCooling intaketemperatureshift–010 Shifts intake temperature by –10°C.–009 Shifts intake temperature by –9°C.–001 Shifts intake temperature by –1°C.0000 No intake temperature shift0001 Shifts intake temperature by +1°C.0009 Shifts intake temperature by +9°C.0010 Shifts intake temperature by +10°C.Automaticstop time afteroperation start0000 Function disabled0001 Stops automatically 5 minutes after operation starts.0002 Stops automatically 10 minutes after operation starts.Can be setin 5-minuteunits.* 0123 Stops automatically 615 minutes after operation starts.0124 Stops automatically 620 minutes after operation starts.0125 Stops automatically 625 minutes after operation starts.7-4. List of Detailed Setting Items7-5