D-42 Parameter ReferenceAC30 series Variable Speed DriveCurrent Sensor TripParameters::Trips::Current Sensor TripThis function contains parameters associated to the missing current sensor detection and trip conditionParameter Name No. Path Default Range Units WritableCurrent Diff Level 1658 Parameters::Trips::Current Sensor Trip 25.00 0.00 to 100.00 % ALWAYSThe percentage of motor rated current which, if exceeded by difference between RMS values of two current sensor measurements,causes this trip to become active. This trip detects missing, or broken connections in the current sensing circuitry that result in loss ofmeasurement of one sensor. Enabled in V/Hz mode of operation only.