D-184 Parameter ReferenceAC30 series Variable Speed DriveTrips HistoryParameters::Trips::Trips HistoryParameter Name No. Path Default Range Units WritableRecent Trips 0895 Parameters::Trips::Trips History NEVERThe Recent Trips array is a record of the last 10 faults that caused the drive to disable the stack. Each entry has the same format asthe First Trip parameter, (see Trips Status). The most recent fault is the first entry in the array, (Recent Trips[0]).Recent Trip Times 1442 Parameters::Trips::Trips History NEVERThe time of each of the recent trips. The time saved is a snapshot of the Control Board Up Time, see Runtime Statistics.Warranty Trips 0968 Parameters::Trips::Trips History NEVERThe Warranty Trips array is a record of the last 3 drive protection trips that were ignored due to the trip being disabled. This will usuallybe because Fire Mode (see Chapter 13) is enabled. Each entry has the same format as the First Trip parameter, (see Trips Status).The most recent fault is the first entry in the array, (Warranty Trips[0]).Warranty Trip Time 0972 Parameters::Trips::Trips History NEVERThe time of each of the Warranty Trips. The time saved is a shapshot of the HV SMPS Up Time, see Runtime Statistics.Warranty Trips Record 1408 Parameters::Trips::Trips History 0:01 OVER VOLTAGE2:03 OVER CURRENT3:04 STACK FAULT4:05 STACK OVER CURRENT7:08 INVERSE TIME10:11 HEATSINK OVERTEMP11:12 INTERNAL OVERTEMP14:15 BRAKE SHORT CCT16:17 BRAKE SWITCH21:22 VDC RIPPLENEVERRecords all drive protection trip event that have been ignored due to the trip being disabled. This will usually be because Fire Mode isenabled. Each entry has the same format as the Active 1 – 32 parameter, (see Trips Status).