5-4 Associated EquipmentAC30 series Variable Speed InverterAC Motor ChokesThe maximum rate of rise of Volts (dv/dt) present on the motor terminals of the inverter, can be as high as 10,000V/s. This can bereduced by adding a motor choke in series with the motor.Installations with long cable runs may suffer from nuisance overcurrent trips, refer to Appendix C Compliance - Cabling Requirements formaximum cable lengths. An output choke may be fitted in the inverter output to limit parasitic capacitive current to earth. Screened cablehas a higher parasitic capacitance to earth and may cause problems in shorter runs. Contact Parker for recommended choke values.Motor Power (kW) Choke Inductance RMS Current Rating Parker Part No.0.751.11.5 2mH 7.5A CO0559312.24.05.5 0.9mH 22A CO0572837.511 0.45mH 33A CO0572841518 0.3mH 44A CO05728522 50μH 70A CO0551933037 50μH 99A CO05525345 50μH 99A CO05525355 50μH 243A CO05796075 50μH 360A CO38788690Contact Parker Hannifin Manufacturing Limited for further information110132