10-6 Trips & Fault FindingAC30V series Variable Speed DriveRuntime AlertsA Runtime Alert is a fault that indicates a permanent hardware error. The Runtime Alert display is of the formRUNTIME ALERTCODE 00000000CODE is a number in the range 0 to 65000. The following value is used to provide additional information to assist Parker Hannifin TechnicalSupport personnel.CODE ERROR Possible Reason for Error1 to255 Internal exception• VCM not secured to power stack• Option not secured correctly to VCM control card• Earth bonding failure.• Fault during firmware upgrade12 Memory access• Attempt to read or write to protected memory. Most likely this will be due to a configuration error. Press OKseveral times until the drive resets correctly, then replace the configuration using PDQ.• Record the error message and contact Technical Support1001to1003Processor overload • Select a lower switching frequency, (Parameters::Motor Control::Pattern Generator::Stack Frequency)• Record the error message and contact Technical Support1006 Memory overflow• Reduce the complexity of the application• Reduce the number of parameters being accessed via the on board Modbus TCP protocol• Reduce the number of parameters being accessed by the fieldbus communications option.1007 Uninitialized pointer • Record the error message and contact Technical Support1010,1101to1111Initialization error • Record the error message and contact Technical Support1200to1299Communications optionerror• Ensure the communications option is correctly fitted• Update the firmware in the AC30.• Replace the communications option1300 Ethernet fault • Record the error message and contact Technical Support