Parameter Reference D-68AC30V series Variable Speed DrivePMAC Motor DataSetup::Motor Control::MotorData PMACParameters::Motor Control::PMAC Motor DataOnly available if PMAC Motor selected in Control Mode.The PMAC Motor Data contains the parameters needed to run and control of a PMAC motor. A PMAC motor is a Permanent Magnet AC Motorwith sinusoidal back EMF.PNO Parameter Descriptions0555 PMAC Max SpeedSet the motor’s rated speed in rpm.0556 PMAC Max CurrentSet the motor’s maximum current ( Amps rms ).0557 PMAC Rated CurrentSet the motor’s rated current ( Amps rms ).Refer to Motor Current Percent in the Feedbacks function. A value of 100% = PMAC rated Current.0558 PMAC Rated TorqueSet the motor’s rated torque.Refer to Actual Torque in the Feedbacks function. A value of 100% = PMAC Rated Torque.0559 PMAC Motor PolesSet the number of motor poles, e.g. for a 4 poles motor enter "4".0560 PMAC Back Emf Const KESet the motor’s Back EMF line to line, rms value (Ke, Volts rms per 1000 rpm)0561 PMAC Winding ResistanceSet the motor’s resistance, line to line at 25 °C.0562 PMAC Winding InductanceSet the motor’s inductance line to line at maximum current. This parameter is used within the current loop and is related to theoverall proportional gain.