10.7 LEVEL_2 ParametertnetnoClobmySretemaraP Range Default Hide/MAX MIN DisplayMain output proportional bandP1 0.0 : ON/OFF control 200.0 0.0 3.0 ---Other values : proportional band settingvalueMain output integral timeI1 0 : disable integral function 3600 0 240 ---Other values : integral time setting valueMain output derivative timeD1 0 : disable derivative function 900 0 60 ---Other values : derivative time setting valueAT.VL Auto tuning offset value 100.0 -100.0 0.0 ---execute auto tuning in (SV-ATVL) pointMain output control cycleCYT1 0 : Linear signal 150 0 10 ---1 : SSR drive2~150 : RelayHysteresis for main outputon/off control use(when P1 = 0.0 appear)heating formula:HYS1 PV ≥ (SV + HYS1) OUT1=OFF 100.0 -100.0 1.0 P1 = 0.0PV ≤ (SV - HYS1) OUT1=ONcooling formula:PV ≥ (SV + HYS1) OUT1=ONPV ≤ (SV - HYS1) OUT1=OFFSub output proportional bandP2 0.0 : ON/OFF control 200.0 0.0 3.0 OUTY = 1Other values : proportional band settingvalueSub output integral timeI2 0 : disable integral function 3600 0 240 OUTY = 1Other values : integral time setting valueSub output derivative timeD2 0 : disable derivative function 900 0 60 OUTY = 1Other values : derivative time setting valueSub output control cycleCYT2 0 : Linear signal 150 0 10 OUTY = 11 : SSR drive2~150 : RelayHYS2 Hysteresis for sub output 100.0 -100.0 1.0 P2 = 0.0on/off control use(when P2 = 0.0 appear)GAP1 Control gap (for main output) 1000 -1000 0 OUTY = 1GAP2 Control gap (for sub output) 1000 -1000 0 OUTY = 1Function or level lockLCK (Please refer to Chapter 10.3 Data Lock 1111 0000 0000 ---Function)FY/FU operation manual 24