5. Setting program execute with wait functionParameter noitpircseDyalpsidDEL Default LevelProgram execution standby temperatureWAIT0 : when program execute do not wait for PV3leveL0.0erutarepmetOther values : when PV=(target SV-WAIT),program entering next segmentWhen program executes, if WAIT=0.0, and SV reaches set temperature, whether PV reaches targettemperature or not, the controller will enter the next segmentWhen program executes, if WAIT value is not 0.0, and SV reaches set temperature, as PV has not reachedtarget temperature, controller will wait for PV temperature to reach SV-WAIT(1) WAIT = 0.0 without wait function setAssume the set temperature of current segment is 100.0°C, and as SV reaches theset temperature of this segment, the controller will enter the next segment(2) WAIT = 5.0 with wait function setAssume the set temperature of current segment is 100.0°C, and as SV reachesthe set temperature of this segment, PV temperature needs to reach 100.0-5.0 (SV-WAIT)=95.0then entering the next segment13.4 Create ProgramThere are 18 sets PTN to choose and each PTN have 8 segments for settingProgram structure diagramLevel 1PV . / SV PTN group setting. Press SET KeyMAX Pattern =18.1 32 181 111MAX Segment =8TIMR RMITRMITRMITSV-1 1-VS1-VS1-VSTM- 1 1-MT1-MT TM- 1OUT1 1TUO1TUO1TUOSV-2 2-VS2-VS2-VSTM- 2 2-MT2-MT TM- 2OUT2 2TUO2TUO2TUO. .... .... ...SV-8 8-VS8-VS8-VSTM- 8 8-MT8-MT TM- 8OUT8 8TUO8TUO8TUOFY/FU operation manual 50