15.2 Input modify to RTDJumper Position Software SettingPlug 2 pcs of Jumper in the left slot as shownParameter set as“INP1=PT1~PT3”RTD calibration flowchartStartSET 2_2 = 1ANL1 = 0ANH1 = 5FFFINP1 = PT1USPL = 850.0LSPL = -199.9Input PT100 signal -199.9°CAdjusts "ANL1" until PV = -199.9Input PT100 signal 850.0°CAdjusts "ANH1" until PV = 850.0Input -199.9°C Check the PV = -199.9Input 850.0°C Check the PV = 850.0NOOK ?YESRepeat step A~E 3~4 timesNO OK ?YESEndSet the range you wantEx: Low = 0.0 , High = 200.0Set LSPL = 0.0 , USPL = 200.0to display ANL1 & ANH1 & DPat Input level (level 3)Step AStep BStep CStep DStep E57 FY/FU operation manual