12.1 Alarm Mode:SV : Alarm set value X:1 / 2 / 3 (There are up to 3 sets of alarms)ALDX Alarm mode Description0 No alarm function Not drive any alarm relays and the corresponding LED lamp.HYSX ONDeviation high OFF1 SV ALX(With hold action) PV ≥ (SV+ALX) → Alarm ONFormula PV ≤ (SV+ALX-HYSA) → Alarm OFFON HYSXDeviation low OFF2 ALX SV(With hold action) *ALX must to be set to a negative valueFormula PV ≤ (SV+ALX) → Alarm ONPV ≥ (SV+ALX+HYSA) → Alarm OFFOFFON HYSX HYSX ON3 Deviation high/low ALX SV ALX(With hold action) PV ≥ (SV+ALX) → Alarm ONFormula PV ≤ (SV-ALX) → Alarm ONPV ≥ (SV-ALX+HYSA) → Alarm OFFPV ≤ (SV+ALX-HYSA) → Alarm OFFONOFF OFFBand ALX SV ALX4 (With hold action) PV ≤ (SV+ALX) → Alarm ONFormula PV > (SV-ALX) → Alarm ONPV ≥ (SV+ALX) → Alarm OFFPV < (SV-ALX) → Alarm OFFHYSX ONProcess high5 OFF(With hold action) ALXFormula PV ≥ ALX→ Alarm ONPV ≤ (ALX-HYSA) → Alarm OFFON HYSXProcess low6 ALXOFF(With hold action)Formula PV ≤ ALX→ Alarm ONPV ≥ (ALX+HYSA) → Alarm OFF7 Segment execute alarmWhen SEG=ALX alarm ON*This mode only available in program type controller8 System error The Alert action, when PV displays error messageActivated conditions:1. Heater current is less the HBAC set valueHBA 2. OUT1 manipulated value exceed 90%3. Conditions of 1 & 2 above are established and continue to(Heater Break Alarm) exceed 20 seconds.9 *Please refer to Chapter 11.4*This mode only available in ALD1 or ALD2Single RAMP Please refer to Chapter 11.7This mode only available in ALD3FY/FU operation manual 44