45 • vacon parametersTel. +358 (0)201 2121 • Fax +358 (0)201 21220588.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)8.6 Digital inputs (Control panel: Menu PAR -> P5)Code Parameter Min Max Unit Default ID NoteP4.1 Ramp shape 0,0 10,0 s 0,0 500 0 = Linear>0 = S-curve ramp timeP4.2 Acceleration time 0,1 3000 s 1,0 103P4.3 Deceleration time 0,1 3000 s 1,0 104P4.4 DC braking current 0.2 xI Nunit2 xI Nunit A Varies 507P4.5 DC braking time atstart 0,00 600.00 s 0 516 0 = DC brake is off atstartP4.6Frequency to startDC braking duringramp stop0,10 10,00 Hz 1,50 515P4.7 DC braking time atstop 0,00 600.00 s 0 508 0 = DC brake is off atstopP4.8 Flux brake 0 3 520 0 = Off 2 = Chopper1 = On 3 = Full modeP4.9 Flux braking cur-rent 0 7,4 A 519P4.10 Ramp shape 2 0,0 10,0 s 0,0 501 0 = Linear>0 = S-curve ramp timeP4.11 Acceleration time 2 0,1 3000 s 1,0 502P4.12 Deceleration time 2 0,1 3000 s 1,0 503Table 8.5: Motor control parametersCode Parameter Min Max Unit Default ID NoteP5.1 Start signal 1 0 6 1 4030 = Not used1 = DI12 = DI2 Only in API FULL& LIMITED3 = DI34 = DI4 Only in API FULL5 = DI56 = DI6P5.2 Start signal 2 0 6 2 404 As parameter 5.1P5.3 Reverse 0 6 0 412 As parameter 5.1P5.4 Ext. fault Close 0 6 0 405 As parameter 5.1Table 8.6: Digital inputsiiiiiiiii