67 • vacon parameter descriptionsTel. +358 (0)201 2121 • Fax +358 (0)201 21220599.5 Digital inputs (Control panel: Menu PAR -> P5)These parameters are programmed using the FTT-method (Function To Ter-minal), where you have a fixed input or output that you define a certain func-tion for. You can also define more than one function to a digital input, e.g. Startsignal 1 and Preset Speed B1 to DI1.The selections for these parameters are:0 = Not used1 = DI12 = DI2 (API FULL & LIMITED)3 = DI3 (API FULL & LIMITED)4 = DI4 (API FULL)5 = DI5 (API FULL)6 = DI6 (API FULL)5.1 S TART SIGNAL 15.2 S TART SIGNAL 25.3 REVERSE5.4 EXTERNAL FAULT ( CLOSE )5.5 EXTERNAL FAULT ( OPEN)5.6 F AULT RESET5.7 RUN ENABLE5.8 PRESET SPEED B05.9 PRESET SPEED B15.10 PRESET SPEED B25.11 DISABLE PI5.12 FORCE TO I/0The control place is forced to I/O by activating the digital input that this func-tion is programmed to.The priority order of selecting control place is1. Navigation wheel2. Forced from I/O3. Parameter 2.15.13 R AMP TIME SELECTIONContact open: Acceleration/Deceleration time 1 selectedContact closed: Acceleration/Deceleration time 2 selectedSet Acceleration/Deceleration times with parameters 4.2 and 4.3 and the al-ternative ramp times with 4.11 and 4.12.