Vacon 100 Application vacon • 12424-hour support +358 (0)201 212 575 • Email: vacon@vacon.com33.3.23 Group 3.10: Automatic resetP3.9.8.2 Analogue input lowfault 0 5 0 7000=No action1=Alarm2=Alarm + preset fault fre-quency (par. P3.9.1.13)3=Alarm + previous fre-quency reference4=Fault (Stop according tostop mode)5=Fault (Stop by coasting)Table 75. Autoreset settingsCode Parameter Min Max Unit Default ID DescriptionP3.10.1 Automatic reset 0 1 0 731 0 = Disabled1 = EnabledP3.10.2 Restart function 0 1 1 719The start mode for Automaticreset is selected with thisparameter:0 = Flying start1 = According to par. P3.2.4P3.10.3 Wait time 0.10 10000.00 s 0.50 717 Wait time before the firstreset is executed.P3.10.4 Trial time 0.00 10000.00 s 60.00 718When the trial time haselapsed, and the fault is stillactive, the drive will trip tofault.P3.10.5 Number of trials 1 10 4 759NOTE: Total number of tri-als (irrespective of faulttype). If the drive is not ableto be reset within this num-ber of trials and the set trialtime a fault will be gener-ated.P3.10.6 Autoreset:Undervoltage 0 1 1 720Autoreset permitted?0 = No1 = YesP3.10.7 Autoreset:Overvoltage 0 1 1 721Autoreset permitted?0 = No1 = YesP3.10.8 Autoreset:Overcurrent 0 1 1 722Autoreset permitted?0 = No1 = YesP3.10.9 Autoreset: AI low 0 1 1 723Autoreset permitted?0 = No1 = YesP3.10.10 Autoreset: Unit over-temperature 0 1 1 724Autoreset permitted?0 = No1 = YesP3.10.11 Autoreset: Motor over-temperature 0 1 1 725Autoreset permitted?0 = No1 = YesTable 74. AI low protection settings