Vacon 100 Application vacon • 9624-hour support +358 (0)201 212 575 • Email: vacon@vacon.com3Figure 24. I/f startTable 39. I/f start parameters3.3.15 Group 3.2: Start/Stop setupStart/Stop commands are given differently depending on the control place.Remote control place (I/O A): Start, stop and reverse commands are controlled by 2 digital in-puts chosen with parameters P3.5.1.1 and P3.5.1.2. The functionality/logic for these inputs isthen selected with parameter P3.2.6 (in this group).Remote control place (I/O B): Start, stop and reverse commands are controlled by 2 digital in-puts chosen with parameters P3.5.1.4 and P3.5.1.5. The functionality/logic for these inputs isthen selected with parameter P3.2.7 (in this group).Local control place (Keypad): Start and stop commands come from the keypad buttons, whilethe direction of rotation is selected by the parameter P3.3.1.9.Remote control place (Fieldbus): Start, stop and reverse commands come from fieldbus.Code Parameter Min Max Unit Default ID DescriptionP3.1.4.12.1 I/f start 0 1 0 534 0 = Disabled1 = EnabledP3.1.4.12.2 I/f start frequency 0.0 P3.1.1.2 Hz 15.0 535Output frequency limitbelow which the defined I/fstart current is fed to motor.P3.1.4.12.3 I/f start current 0.0 100.0 % 80.0 536The current fed to the motorwhen the I/f start function isactivated.Motor CurrentTime [s]I/f StartFrequencyI/f Start CurrentOutput Frequency9240.emf