vacon • 65 Vacon 100 ApplicationTel. +358 (0) 201 2121 • Fax +358 (0)201 212 20533.2.5 Multi-Purpose Control ApplicationMulti-Purpose control application provides a wide range of parameters for controlling motors.It can be used for various kinds of different processes, where a wide range of motor controltuning functions are needed (e.g. conveyors).Drive can be controlled either from Keypad, Fieldbus or I/O terminal. In I/O terminal control,start/stop commands are given through DI1 and DI2 and frequency reference either from AI1or AI2.Two acceleration/deceleration ramps are available. Selection between Ramp1 and Ramp2 isdone by DI6.All drive outputs are freely configurable. One analog output (Output Frequency) and three relayoutputs (Run, Fault, Ready) are available on the basic I/O board.Control connectionsMulti-Purpose control application default control connections.1.34.7 Sleep FrequencyLimit 1 0.0 320.0 Hz 0.0 1016Drive goes to sleep modewhen the output frequencystays below this limit for atime greater than thatdefined by parameter Sleepdelay.1.34.8 Sleep Delay 1 0 3000 s 0 1017The minimum amount oftime the frequency has toremain below the Sleep levelbefore the drive is stopped.1.34.9 Wake-up Level 1 Varies Varies Varies Varies 1018Defines the level for the PIDfeedback value wake-upsupervision. Uses selectedprocess units.1.34.10 Preset Frequency 1 P1.3 P1.4 Hz 10,0 105 Preset Frequency selected bydigital input DI5.Code Parameter Min Max Unit Default ID Description