9 MONITORING VALUE DESCRIPTIONSThis chapter gives you the basic descriptions of all monitoring values.9.1 BASICV2.2.1 OUTPUT FREQUENCY (ID 1)This monitoring value shows the actual output frequency to the motor.V2.2.2 FREQUENCY REFERENCE (ID 25)This monitoring value shows the actual frequency reference to the motor control.The value is updated at 10 ms interval.V2.2.3 MOTOR SPEED (ID 2)This monitoring value shows the actual speed of the motor in rpm (calculated value).V2.2.4 MOTOR CURRENT (ID 3)This monitoring value shows the measured current of the motor.The scaling of the value is different for different drive sizes.V2.2.5 MOTOR TORQUE (ID 4)This monitoring value shows the actual torque of the motor (calculated value).V2.2.7 MOTOR SHAFT POWER (ID 5)This monitoring value shows the actual shaft power of the motor (calculated value) as apercentage of the motor nominal power.V2.2.8 MOTOR SHAFT POWER (ID 73)This monitoring value shows the actual shaft power of the motor (calculated value).The unit of measurement is kW or hp, depending on the 'kW/hp Selection' parameter value.V2.2.9 MOTOR VOLTAGE (ID 6)This monitoring value shows the actual output voltage to the motor.V2.2.10 DC LINK VOLTAGE (ID 7)This monitoring value shows the measured voltage in the DC-link of the drive.V2.2.11 UNIT TEMPERATURE (ID 8)This monitoring value shows the measured heatsink temperature of the drive.The unit of the monitoring value is celsius degrees or fahrenheit degrees, depending on the'C/F Selection' parameter value.MONITORING VALUE DESCRIPTIONS VACON · 10524-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 9