P3.7.7 RAMP TIME FACTOR (ID 518)Use this parameter to set the multiplier of the selected ramp times when the outputfrequency of the drive is between the prohibited frequency limits.The Ramp Time Factor sets the acceleration and the deceleration time when the outputfrequency is in a prohibited frequency range. The value of the Ramp Time Factor is multipliedwith the value of P3.4.2 (Acceleration Time 1) or P3.4.3 (Deceleration Time 1). For example,the value 0.1 makes the acceleration/deceleration time ten times shorter.ABCDEF [s][Hz]Fig. 27: The parameter Ramp Time FactorA. Output FrequencyB. High LimC. Low LimD. Ramp Time Factor = 0.3E. Ramp Time Factor = 2.5F. Time10.8 LIMIT SUPERVISIONSP3.8.1 SUPERVISION #1 ITEM SELECTION (ID 1431)Use this parameter to select the supervision item.The output of the supervision function can be selected to the relay output.P3.8.2 SUPERVISION #1 MODE (ID 1432)Use this parameter to set the supervision mode.When the 'Low limit' mode is selected, the output of the supervision function is active whenthe signal is below the supervision limit.When the'High limit' mode is selected, the output of the supervision function is active whenthe signal is above the supervision limit.P3.8.3 SUPERVISION #1 LIMIT (ID 1433)Use this parameter to set the supervision limit for the selected item.The unit shows automatically.PARAMETER DESCRIPTIONS VACON · 15124-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM 10