2 WIZARDS2.1 PID MINI-WIZARDThe application wizard helps you to set the basic parameters that are related to theapplication.To start the PID mini-wizard, set the value Activate to parameter P1.17 PID Mini-Wizard in theQuick Setup menu.The default settings tell you to use the PID controller in the one feedback / one setpointmode. The default control place is I/O A, and the default process unit is %.1 Make selections for Process unit (P3.12.1.4) More than 1 selection.If your selection is other than %, you see the next questions. If your selection is %, the wizardgoes directly to question 5.2 Set a value for Process Unit Min (P3.12.1.5) The range depends on the selection in ques-tion 1.3 Set a value for Process Unit Max (P3.12.1.6) The range depends on the selection in ques-tion 1.4 Set a value for Process Unit Decimals (P3.12.1.7) Range: 0-45 Set a value for Feedback 1 Source Selection(P3.12.3.3)See Table 34 Feedback settings.If you make a selection of an analogue input signal, you see the question 6. With otherselections, the wizard goes to question 7.6Set the signal range of the analogue input0 = 0-10V / 0…20mA1 = 2-10V / 4…20mASee Table 15 Analogue input settings.7Set a value for Error Inversion (P3.12.1.8)0 = Normal1 = Inverted8 Set a value for Setpoint Source Selection (P3.12.2.4) See Table 33 Setpoint settings.If you make a selection of an analogue input signal, you see the question 9. With otherselections, the wizard goes to question 11.If you set Keypad Setpoint 1 or Keypad Setpoint 2 for the value, the wizard goes directly toquestion 10.VACON · 20 WIZARDS2 TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205