659 Diagnosis, asset management and serviceVEGAPULS 69 • 4 … 20 mA/HART - two-wire47247-EN-150211CodeText mes-sageCause RectificationF125Impermissi-ble electronicstemperature– Temperature of the elec-tronics in the non-specifiedrange– Check ambient temperature– Isolate electronics– Use instrument with highertemperature rangeF260Error in thecalibration– Error in the calibration car-ried out in the factory– Error in the EEPROM– Exchanging the electronics– Send instrument for repairF261Error in theinstrumentsettings– Error during setup– False signal suppressionfaulty– Error when carrying out areset– Repeat setup– Carry out a resetF264Installation/Setup error– Adjustment not within thevessel height/measuringrange– Max. measuring range ofthe instrument not sufficient– Check or correct installationand/or parameter adjust-ment– Use an instrument with big-ger measuring rangeF265Measurementfunction dis-turbed– Sensor no longer carriesout a measurement– Operating voltage too low– Check operating voltage– Carry out a reset– Disconnect operating volt-age brieflyThe following table shows the error codes and text messages in thestatus message "Function check" and provides information on causesas well as corrective measures.CodeText mes-sageCause RectificationC700Simulation ac-tive– A simulation is active – Finish simulation– Wait for the automatic endafter 60 mins.The following table shows the error codes and text messages in thestatus message "Out of specification" and provides information oncauses as well as corrective measures.CodeText mes-sageCause RectificationS600Impermissi-ble electronicstemperature– Temperature of the elec-tronics in the non-specifiedrange– Check ambient temperature– Isolate electronics– Use instrument with highertemperature rangeFunction checkOut of specification PreviousNext |