118 Commissioning WAGO-I/O-SYSTEM 750750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.4.0, valid from HW/SW Version 01/01Pos: 47.20 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Parametrieren mit WAGO-I/O-CHECK/Parametrieren 750-66x/Parameter Betriebsart 750-66x/000-003 @ 6\mod_1260799699850_21.docx @ 47114 @ 4 @ 18.3.4.7 Parameter Operating ModeEvaluation of the input signal state in the "Rotary table" operating mode!If you have set the Operating mode to the "Rotary table" value, the temporallogic evaluation of the signal state must be performed by a suitable function blockin the safe PLC. Under certain circumstances, you can use the process image ofthe digital inputs without the suitable function blocks.An overview for using PROFIsafe I/O modules in combination with a safe PLC issummarized in an application note. This application note is available on theInternet at www.wago.com in the area "Service > Documentation > ApplicationNotes...".You can use the Operating mode parameter to choose between safe standardanalysis of the digital inputs (single-channel, two-channel) and the specific"Rotary table" operating mode.If you want to use the digital inputs single-channel or two-channel, you must setthe Operating mode parameter to the "Standard" value.The choice of operating mode only affects the digital inputs and clock outputs ofthe PROFIsafe I/O module.If you want to connect the cam switch of a rotary table or one or more operatingmode selector switches to the digital inputs of the PROFIsafe I/O module, youhave to set the parameter to the "Rotary table" value.If you set the Operating mode parameter to "Round table", the PROFIsafe I/Omodule behaves as follows:• The Dual channel parameter is only accepted by the PROFIsafe I/O modulewith the "no" value.• The Short circuit test parameter is only accepted by the PROFIsafe I/Omodule with the "active" value.• All inputs are sensitive to clock output T1 and are tested for short circuit onany 24 V signal source.• Clock output T2 is switched off.• The signal states on the digital inputs are not analyzed by the PROFIsafe I/Omodule.Pos: 47.21 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1