WAGO-I/O-SYSTEM 750 Commissioning 119750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.4.0, valid from HW/SW Version 01/01Pos: 47.22 /Serie 750 (WAGO-I/O-SYSTEM)/In Betrieb nehmen/Parametrieren mit WAGO-I/O-CHECK/Parametrieren 750-66x/Parameter Ausgangskonfiguration 750-0666/000-003 @ 10\mod_1305884071499_21.docx @ 73044 @ 45555 @ 18.3.4.8 Parameter Output ConfigurationThe Output Configuration parameter is used to define the wiring used for theload or loads to digital power outputs O1 and O2. Digital power output O2 isdesigned, so that it can be used to switch the 24 V potential (H-Side) or to switchthe 0 V potential of the field supply voltage (L-Side). Digital output O2 can onlybe used to switch the 24 V potential.Four different output configurations are possible with the PROFIsafe I/O module750-666/000-003 for single-channel or two-channel switching.8.3.4.8.1 Output Configuration “H-Side/L-Side 1”If you have set the Output Configuration parameter to the value "H-Side/L-Side 1", then the PROFIsafe I/O module switches the 24 V and 0 V potential ofthe field supply voltage. The load is switched two-channel and separatedcompletely from the field supply voltage. Connect the load between connectionO1B and O2A. Connection O2B is connected to the 0 V potential of the fieldvoltage supply. The load is switched using the bit 0 of the output process image.Figure 46: Output Configuration “H-Side/L-Side 1”Read the section “Connect Devices” > … > “Output Configuration “H-Side/L-Side 1””.Diagnostic wiring error with output configuration “H-Side/L-Side 1”If you have set the Output Configuration parameter to the value "H-Side/L-Side 1", then you have to connect connection O2B to the 0 V potential of the fieldsupply voltage. Otherwise, the PROFIsafe I/O module identifies an error and the"Wiring error" diagnostic message appears.The PROFIsafe I/O module identifies the wiring error only when switching onboth outputs O1 and O2.