78 Connect Devices WAGO-I/O-SYSTEM 750750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.4.0, valid from HW/SW Version 01/01In the output configuration "H-Side/H-Side 1", the PROFIsafe I/O moduleswitches both semiconductor switches ON or OFF at the same time using the bit 0of the output process image.You must disable line break detection by setting the Line break detectionparameter to "inactive". For more information about configuring the PROFIsafeI/O module, read section "Parameterization of the PROFIsafe I/O Module with theWAGO Parameterization Tool".You can achieve a risk reduction of SIL3/Cat.4/PL e, for example, by readingback the switching states of the power jumper contacts from positively drivencontacts of a relay.Line break detection on the digital outputMonitoring of line breaks only works between connections O1B and O2A. If youset the Output Configuration parameter to the value "H-Side/L-Side 1", thenyou have to set the value of the Line break detection to the value "inactive".Line break detection is not safety related and cannot be part of the safety functionunder any circumstances.Use the same value for the output tolerance time of output O1 and O2!If the Output Configuration parameter is set to "H-Side/L-Side 1", the values ofthe Output tolerance time for both outputs O1 and O2 must be set to the samevalue. This is checked by the PROFIsafe I/O module during the parameterizationprocedure and a suggested correction is indicated by the PROFIsafe I/O module inthe WAGO parameterization tool in case of deviation.Use the same value for the test pulse duration of output O1 and O2!If the Output Configuration parameter is set to "H-Side/L-Side 1", the values ofthe Test pulse duration for both outputs O1 and O2 must be set to the samevalue. This is checked by the PROFIsafe I/O module during the parameterizationprocedure and a suggested correction is indicated by the PROFIsafe I/O module inthe WAGO parameterization tool in case of deviation.Pos: 39.45 /Serie 750 (WAGO-I/O-SYSTEM)/Anschließen/Anschlussbeispiele/Sonderklemmen/Anschlussbeispiele 750-066x PROFIsafe/Anschlussbeispiele 750-0666/000-003 Hinweis: Ausgangstoleranzzeit nicht kleiner als Testpulsdauer! @ 10\mod_1304926664366_21.docx @ 72644 @ @ 1The value of the output tolerance time must not be less that the value of thetest pulse duration!The value of the Output tolerance time parameter may not be less than the valueof the Test pulse duration parameter. This is checked by the PROFIsafe I/Omodule during the parameterization procedure and a suggested correction isindicated by the PROFIsafe I/O module in the WAGO parameterization tool incase of deviation.Pos: 39.46 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1