WAGO-I/O-SYSTEM 750 Diagnostics 139750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iParManualVersion 1.4.0, valid from HW/SW Version 01/01Table 45: Diagnostic MessagesAlarm DescriptionInvalidF_WD_TimeDiagnostictype Module DiagnosticsCoding 0x0043LEDindicationGroup error (E) redPROFIsafe (G) redSolutionThe monitoring time for the fail-safe dataexchange must be set to a value greaterthan 0 ms. Correct the F parameterization.UndervoltageDiagnostictype Module DiagnosticsCoding 0x0202LEDindication Group error (E) redSolutionThe 24V field supply of the F I/O moduleis below the specified tolerance. Correctthe voltage supply responsible.Undervoltage PWRDiagnostictype Module DiagnosticsCoding 0x0220LEDindication Group error (E) redSolutionThe 24V power supply of the F I/O moduleis below the specified tolerance. Correctthe voltage supply responsible. Check forshort circuit.Wiring errorDiagnostictype Channel DiagnosticsCoding 0x021DLEDindicationStatus On (I or K) red,group error (E) redSolutionThe wiring of output O2 does notcorrespond to the selected outputconfiguration. Correct either the outputconfiguration or the wiring.Pos: 52.4 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1