WAGO-SPEEDWAY 767 Diagnostics 101767-5204 MOVILINK® Interface (RS-232, RS-485)ManualVersion 1.1.0Pos : 44.7 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebs mel dungen 767- 5204 F, I/O (Pos. 16 + 17) @ 14\mod_1357824357686_21.doc x @ 108282 @ @ 1Table 57: Operational messages 2No. LED Color/status Cause Remedy/information16 FRed There is at least one globaldiagnostic message on themodule.Check the supply voltages U LSand U A of the upstream 767Series components. For moreinformation, see the section"Parameterizing">"Diagnostic Overview".17Ch 1.1Ch 2.1Off No data to send Check the connection of theexternal device and that thetransmission parametersmatch.Yellow flashing Channel sends data ---Ch 1.2Ch 2.2Off No data receipt Check the connection of theexternal device and that thetransmission parametersmatch.Yellow flashing Channel receives data ---17 0 ... 3Yellow Input: Signal active and isrecognized as '1'.---Output: Output signal isactive.Check the actuator connectionfor short circuit/overload. Ashort circuit or overload canonly occur when the output isswitched on.Red* Error on output Check the actuator connectionfor short circuit/overload.* If you set the time of the parameter "Restart delay, actuator" (section"Parameterizing"> "Output Parameters") to 0 ms, the I/O LED appears yellowrather than red in case of a short circuit or overload due to the short restartinterval.Pos : 44.8 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebs mel dungen 767- xxxx U LS und UA (Pos. 18 + 19) @ 8\mod_1278577022948_21.doc x @ 59316 @ @ 118 U AGreen Actuator supply U A ispresent.-Off Actuator supply U A is notpresent.Connect the power supply andcheck the voltage level, ifapplicable.19 U LSGreen Logic supply and sensorsupply U LS are present.-Off Logic supply and sensorsupply U LS are not present.Connect the power supply andcheck the voltage level, ifapplicable.Pos : 45 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1