B Parameter List134 YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide■ b4: Timer Function■ b5: PID Controlb3-10 Speed Search DetectionCompensation GainSets the gain which is applied to the speed detected by Speed Estimation SpeedSearch before the motor is reaccelerated. Increase this setting if ov occurs whenperforming Speed Search after a relatively long period of baseblock.Default: 1.05Min: 1.00Max: 1.20b3-14 Bi-Directional Speed SearchSelection0: Disabled (uses the direction of the frequency reference)1: Enabled (drive detects which way the motor is rotating)Default: <10>Min: 0Max: 1b3-17 Speed Search Restart CurrentLevelSets the Speed Search restart current level as a percentage of the drive ratedcurrent.Default: 150%Min: 0%Max: 200%b3-18 Speed Search RestartDetection Time Sets the time to detect Speed Search restart.Default: 0.10 sMin: 0.00 sMax: 1.00 sb3-19 Number of Speed SearchRestartsSets the number of times the drive can attempt to restart when performing SpeedSearch.Default: 3Min: 0Max: 10b3-24 Speed Search MethodSelection0: Current Detection1: Speed EstimationDefault: 0Min: 0Max: 1b3-25 Speed Search Wait Time Sets the time the must wait between each Speed Search restart attempt.Default: 0.5 sMin: 0.0 sMax: 30.0 s<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).<10> Default setting is determined by the control mode (A1-02).No. Name Description Settingb4-01 Timer Function On-DelayTime Used to set the on-delay and off-delay times for a digital timer output (H2-=12). The output is triggered by a digital input programmed to H1-=18)Default: 0.0 sMin: 0.0 sMax: 3000.0 sb4-02 Timer Function Off-DelayTimeDefault: 0.0 sMin: 0.0 sMax: 3000.0 sNo. Name Description Settingb5-01 PID Function Setting0: Disabled1: Enabled (PID output becomes output frequency reference, deviation Dcontrolled)2: Enabled (PID output becomes output frequency reference, feedback Dcontrolled)3: Enabled (PID output added to frequency reference, deviation D controlled)4: Enabled (PID output added to frequency reference, feedback D controlled)Default: 0Min: 0Max: 4b5-02 Proportional Gain Setting (P) Sets the proportional gain of the PID controller.Default: 1.00Min: 0.00Max: 25.00b5-03Integral Time Setting (I) Sets the integral time for the PID controller.Default: 1.0 sMin: 0.0 sMax: 360.0 sb5-04Integral Limit Setting Sets the maximum output possible from the integrator as a percentage of themaximum output frequency.Default: 100.0%Min: 0.0%Max: 100.0%b5-05Derivative Time (D) Sets D control derivative time.Default: 0.00 sMin: 0.00 sMax: 10.00 sb5-06PID Output Limit Sets the maximum output possible from the entire PID controller as a percentageof the maximum output frequency.Default: 100.0%Min: 0.0%Max: 100.0%b5-07PID Offset Adjustment Applies an offset to the PID controller output. Set as a percentage of themaximum output frequency.Default: 0.0%Min: -100.0%Max: 100.0%No. Name Description Setting