B Parameter List172 YASKAWA ELECTRIC TOEP C710616 21C YASKAWA AC Drive - A1000 Quick Start Guide◆ q: DriveWorksEZ Parameters◆ r: DriveWorksEZ Connection Parameters◆ T: Motor TuningEnter data into the following parameters to tune the motor and drive for optimal performance■ T1: Induction Motor Auto-Tuningo4-13 Number of Run CommandsCounter Initialization0: Number of Run commands counter is not reset when the drive is initialized(A1-03).1: Number of Run commands counter is reset when the drive is initialized (A1-03).Default: 0Min: 0Max: 1No. Name Description Settingq1-01 to q6-07 DriveWorksEZ Parameters Reserved for DriveWorksEZ Refer to Help in theDWEZ software.No. Name Description Settingr1-01 tor1-40DriveWorksEZ ConnectionParameters 1 to 20 (upper/lower)DriveWorksEZ Connection Parameters 1 to 20 (upper/lower)Default: 0Min: 0Max: FFFFHNo. Name Description SettingT1-00 Motor 1 / Motor 2 Selection 1: Motor 1 (sets E1-, E2-)2: Motor 2 (sets E3-, E4-)Default: 1Min: 1Max: 2T1-01<37> Auto-Tuning Mode Selection0: Rotational Auto-Tuning1: Stationary Auto-Tuning 12: Stationary Auto-Tuning for Line-to-Line Resistance3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings andSpeed Estimation Speed Search)4: Stationary Auto-Tuning 28: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-Tuning)Default: 0Min: 0Max: 4, 8, 9 <10>T1-02 Motor Rated PowerSets the motor rated power as specified on the motor nameplate.Note: Use the following formula to convert horsepower into kilowatts: kW =HP x 0.746.Default: <6>Min: 0.00 kWMax: 650.00 kWT1-03<18> Motor Rated Voltage Set the motor rated voltage as specified on the motor nameplate.Default: 200.0 VMin: 0.0 VMax: 255.0 VT1-04 Motor Rated Current Sets the motor rated current as specified on the motor nameplate.Default: <6>Min: 10% of driverated currentMax: 200% of driverated currentT1-05 Motor Base Frequency Sets the rated frequency of the motor as specified on the motor nameplate.Default: <46>Min: 0.0 HzMax: 400.0 HzT1-06 Number of Motor Poles Sets the number of motor poles as specified on the motor nameplate.Default: 4Min: 2Max: 48T1-07 Motor Base Speed Sets the rated speed of the motor as specified on the motor nameplate.Default: <47>Min: 0 r/minMax: 24000 r/minT1-08 PG Number of Pulses PerRevolutionSet the number of pulses per revolution for the PG being used (pulse generatoror encoder).Default: <45>Min: 0 pprMax: 60000 pprNo. Name Description Setting