You get valid IP address parameters from your system administrator. The assignment ofthe IP address data happens online in the Siemens SIMATIC Manager starting with ver-sion V 5.5 & SP2 with the following proceeding:1. Start the Siemens SIMATIC Manager and set via ‘Optionsè Set PG/PC interface’the access path to ‘TCP/IP -> Network card ....’ .2. Open with ‘PLC è Edit Ethernet Node n’ the dialog window with the same name.3. To get the stations and their MAC address, use the [Browse] button or type in theMAC Address. The Mac address may be found at the 1. label beneath the front flapof the CPU.4. Choose if necessary the known MAC address of the list of found stations.5. Either type in the IP configuration like IP address, subnet mask and gateway.6. Confirm with [Assign IP configuration].ð Direct after the assignment the Ethernet PG/OP channel may be reached onlineby these address data. The value remains as long as it is reassigned, it is over-written by a hardware configuration or an factory reset is executed.4.6.1 Take IP address parameters in projectFrom firmware version V. 2.4 and up, you have the following options for configuring theEthernet PG/OP channel:n Configuration via integrated CPU interface (firmware version V. 2.4 and up only).n Configuration via additional CP (all firmware versions).4.6.1.1 Configuration via integrated CPU interfaceFrom firmware version V. 2.4 this variant for configuration is recommended. The followingadvantages result:n The configuration becomes clearer, because the periphery modules and thePROFINET IO devices are configured on the PROFINET line of the CPU and no addi-tional CP is to be configured.n There are no address collisions, because the S7 addresses for all components areassigned from the address area of the CPU.Unless during the hardware configuration of the CPUÄ 68 there was no IP address dataassigned yet or these are to be changed, the configuration happens to the following pro-ceeding, otherwise the Ethernet PG/OP channel is configured.1. Open the Siemens hardware configurator and, if not already done, configure theSiemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).2. Open the PROFINET Properties dialog box of the CPU by double-clicking ‘PN-IO’ .3. Click at ‘General’ .4. At ‘Properties’ , enter the previously assigned IP address data and a subnet. The IPaddress data are not accepted without subnet assignment!Assign IP address param-eters2 variants for configura-tionProceedingVIPA System MICRODeployment CPU M13-CCF0000Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in projectHB400 | CPU | M13-CCF0000 | en | 18-5072