2. D [GITAL, OPERATdR (JNfOP-114) (Confd)" Setting ErrorIn the following cases, the set value blinks for 3seconds and the data before changing are returned.When a value exceeding the setting range is setIf the following condition is not satisfied in themultifunction input selection constant settingMultifunction input selection 1 (No. 32)=Multifunctioninput selection 2 (No. 33)Multifunction input selection 1 (No.32)=Multifunctioninput selection 3 (No.34)Multifunction input selection 2 (No.33)=Multifunctioninput selection 3 (No.34)If the following conditions are not satisfied in the V/fconstant settingMax. output frequency (No. 02)!'=-= Max. voltageoutput frequency (No. 04) >Mid. output frequency(No.05) - Min. voltage output frequency (No . 07)For the following setting, intermediate outputfrequency voltage (No . 06) is disregardedIntermediate output frequency = Min . outputfrequency.For details, refer to "V/f CHARACTERISTICSETTING" on page 102.If the following condition is not satisfied in thefrequency reference constant settingSet frequency reference (NoS. 13 to 17) ,.5 Max . outputfrequency (No. 02) X Output frequency upper limitvalue (No. 24)For details, refer to "V/f CHARACTERISTICSETTING" on page 102 and "OUTPUTFREQUENCY LIMIT" on page 111 .If the following condition is not satisfied in thefrequency reference upper / lower limit value settingFrequency reference lower limit value (No. 25)s Frequency reference upper limit value (No. 24)21