9.9 Controller Setup9.9.1 PIN protection activate, PIN 0010PIN ProtectionThe adjustments for the installation in the service level can be protected againstunintentional modifications. To do this, activate the “PIN protection” = “ON”.In order to simplify the initial start-up operation, the service level in the factory setting isfree = “OFF” i.e. accessible without PIN 0010.InformationAfter installation of the device has been carried out, “PIN-Protection” should be activated = “ON”9.9.2 PIN protection activate, PIN 1234Set protectionThe “Settings” menu for the user’s basic settings (Setpoint, default value, min, max ..)are freely accessible when using the factory settings (i.e. without “PIN”).If necessary, these can also be protected against unauthorized modifications by usinga “PIN 1234” . For this, the settings protection must be programmed to “ON”. Thesettings menu is then no longer visible without inputting a PIN!Function only in combination with activated PIN-Protection!9.9.3 Save user settings restore with PIN 9090Save User SetupThe individually made device configurations (User Setting) can be saved here (corre-sponds to PIN 9091).By entering PIN 9090 the individually made device configurations can be reestablished( Start - PIN Input).InformationBy entering “PIN 9095” in the “PIN” menu in the “start” menu-group, the device is entirelyreset to the pre-delivery condition.Any changes that have been made to the settings are thus lost!9.9.4 Sensor Alarm ON / OFFFunction only in controller mode ( 2.01 )!For “E1 Analog In” and if activated for sensor 2 “E2 Analog In”.In case of an interruption or short-circuit in the sensor conductor, or in case of measured values thatlie outside of the device’s measurement range, a time-delayed fault indication takes place.Alarm sensorsWith “Alarm Sensors” = “OFF” (factory setting). Indicatedsensor disturbances are displayed as “Message” alternatingto the actual value and stored in the menu of “Events”. Sensor 1Alarm sensorsWith “AlarmSensors” = “ON” areindicated sensor disturban-ces as “Alarm” alternating to the actual value and stored inthe menu of “Events”.Indication via relays is possible ( IO Setup / function relayoutputs).Sensor 1Operating Instructions Icontrol – model series FXDM ProgrammingL-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB45/96