9.11.2 Limit indication depending on setting or sensor signalLmt E1 FunctionFollowing functions can be allocated to the limit indicationOFF without function1L Indication with the centralized fault of a programmed relay (IO allocationFunction |2K|).Warning symbol in display, “AL” code in events memory.2L Is merely displayed in the events menu as message “msg”.In the IO setup, a separate relay can be allocated independent of these settings.Lmt E1 minBoth values for E1 (“E1 min” and “E1 max”) can be set independent of each other andact on a relay together if correspondingly programmed. If a function is activated or if arelay is allocated, both settings (“min” and “max”) are initially at “OFF”.Work can be carried out with one as well as with both limit indicators.The same setting applies to “E2 Min.” and “E2 Max.”, described below for “E1”.Undercutting the signal (“E1 min”).If the signal undercuts the set value “E1 min”, this is reported until the set value (plusadjustable hysteresis) has been exceeded once again.Exceeding the signal (“E1 max”).If the signal exceeds the set value “E1 max”, this is reported until the set value (minushysteresis) has been undercut once again.Lmt E1 maxLmt E1 Hyst.E1 HysteresisHysteresis adjustment in the unit of measure of the programmed input signal.Lmt E1 Del.E1 DelayTime delay exceeding “Level max.” up to indication by relay and alarm symbol.Setting range: 0 - 120 sec.Factory setting: 2 sec.InformationAlways adjust the value for the maximum input signal higher than the value for the minimum inputsignal!E1 Max. > E1 Min.Example for a limit indication of default signal or sensor signal to “Analog In 1”50 %Analog IN01100 %111.05.2007v_grenzwert_signal_k1_1.vsdSettings:- E1 Max.: 80 %- E1 Min.: OFF- switching hysteresis 5 % (from100 %)50 %Analog IN01100 %211.05.2007v_grenzwert_signal_k1_2.vsdSettings:- E1 Min.: 20 %- E1 Max.: OFF- switching hysteresis 5 % (from100 %)50 %Analog IN01100 %311.05.2007v_grenzwert_signal_k1_3.vsdSettings:- E1 Min.: 20 %- E1 Max.: 80 %- switching hysteresis 5 % (from100 %)Terminal “E1” and “GND” alarm via relay “K1” (non-inverted) IO Setup → K1 function: |5 K| = limitindicatorsOperating Instructions Icontrol – model series FXDM ProgrammingL-BAL-E036-GB 1422 Index 008 Part.-No. 00154773-GB64/96