NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters84 BU 0135 en-41185.2.1 Operating displaysP000 Operating display RDDisplay range 0.01 … 9999 Other applicable parameter(s): P001Description In the SimpleBox (SK CSX-3H) display, the operating value selected in parameteronline is displayed.P001 Selection of display value RMSetting range 0 … 11 Other applicable parameter(s): P000Factory setting { 0 }Description Selection of the operating value to be displayed (see P000)Setting values Value Meaning0 Actual frequency [Hz] Output frequency currently being supplied by device1 Nominal frequency [Hz] Frequency of mains voltage that is currently present2 Current [A] Current output current measured by device3 Effective current [A] Effective current currently being supplied by device4 Reactive current [A] Reactive current currently being supplied by device5 Mains voltage [V] Voltage currently being measured at the input terminals6 cos Phi [-] Calculated value of current power factor7 Apparent power KVA Calculated value of current apparent power8 Effective power [kW] Calculated value of current effective power9 Mains phase sequence [-] 0 = Clockwise rotating field1 = Counter-Clockwise rotating field10 Duty factor [%] Phase angle control value currently being achieved by device.0 % = "Motor off", 100 % = "Motor voltage = Mains voltage"11 Actual currentamplification[%] Actual measured current in relation to the measurement rangeP003 Supervisor code RMSetting range 0 … 9999Factory setting { 1 }Description The scope of the visible parameters can be influenced by setting the supervisor code.Setting values Value Meaning0 Supervisor mode off The supervisor parameters are not visible.1 Supervisor mode on All parameters are visible.2 … Supervisor mode off The supervisor parameters are not visible.