Parameters 1171010 Standard DI, RO Configuration of digital inputs and relay outputs.10.02 DI delayed status Displays the status of digital inputs DI1…DI6. Bits 0…5 reflectthe delayed status of DI1…DI6.Example: 0000000000010011b = DI5, DI2 and DI1 are on,DI3, DI4 and DI6 are off.This word is updated only after a 2 ms activation/deactivationdelay. When the value of a digital input changes, it mustremain the same in two consecutive samples, that is for 2 ms,for the new value to be accepted.This parameter is read-only.-0000h…FFFFh Delayed status for digital inputs. 1 = 110.03 DI force selection The electrical statuses of the digital inputs can be overriddenfor eg. testing purposes. A bit in parameter 10.04 DI forceddata is provided for each digital input, and its value is appliedwhenever the corresponding bit in this parameter is 1.Note: Boot and power cycle reset the force selections(parameters 10.03 and 10.04).0000h0000h…FFFFh Override selection for digital inputs. 1 = 1No. Name/Value Description Def/FbEq16Bit Name Description0 DI1 1 = Digital input 1 is ON.1 DI2 1 = Digital input 2 is ON.2 DI3 1 = Digital input 3 is ON.3 DI4 1 = Digital input 4 is ON.4 DI5 1 = Digital input 5 is ON.5 DI6 1 = Digital input 6 is ON.6…15 ReservedBit Value0 1 = Force DI1 to value of bit 0 of parameter 10.04 DI forced data. (0 = Normal mode)1 1 = Force DI2 to value of bit 1 of parameter 10.04 DI forced data. (0 = Normal mode)2 1 = Force DI3 to value of bit 2 of parameter 10.04 DI forced data. (0 = Normal mode)3 1 = Force DI4 to value of bit 3 of parameter 10.04 DI forced data. (0 = Normal mode)4 1 = Force DI5 to value of bit 4 of parameter 10.04 DI forced data. (0 = Normal mode)5 1 = Force DI6 to value of bit 5 of parameter 10.04 DI forced data. (0 = Normal mode)6…15 Reserved