Parameters 28796.102 User lockfunctionality(Visible when user lock is open)Selects the actions or functionalities to be prevented by theuser lock. Note that the changes made take effect only whenthe user lock is closed. See parameter 96.02 Pass code.Note: We recommend you select all the actions andfunctionalities unless otherwise required by the application.0000h0000h…FFFFh Selection of actions to be prevented by user lock. -9797 Motor control Switching frequency; slip gain; voltage reserve; flux braking;anti-cogging (signal injection); IR compensation.97.01 Switchingfrequency referenceDefines the switching frequency of the drive that is used aslong as the drive stays below the thermal limit. See sectionSwitching frequency on page 79.Higher switching frequency results in lower acoustic motornoise. Lower switching frequency generates less switchinglosses and reduce EMC emissions.Note: If you have a multimotor system, contact your localABB representative.4 kHz2 kHz 2 kHz. 2No. Name/Value Description Def/FbEq16Bit Name Information0 Disable ABB accesslevels1 = ABB access levels (service, advanced programmer, etc.; see96.03) disabled1 Freeze parameterlock state1 = Changing the parameter lock state prevented, ie. pass code358 has no effect2 Disable filedownload1 = Loading of files to drive prevented. This applies to• firmware upgrades• parameter restore• loading an adaptive program• changing home view of control panel• editing drive texts• editing the favorite parameters list on control panel• configuration settings made through control panel such astime/date formats and enabling/disabling clock display.3…10 Reserved11 Disable OEM accesslevel 11 = OEM access level 1 disabled12 Disable OEM accesslevel 21 = OEM access level 2 disabled13 Disable OEM accesslevel 31 = OEM access level 3 disabled14…15 Reserved