Parameters 27380.61 Q value Q2 Defines the flow rate at point 2 on the PQ performance curve.See parameter 80.60 Q value Q1 (page 272).0.0080.62 Q value Q3 Defines the flow rate at point 3 on the PQ performance curve.See parameter 80.60 Q value Q1 (page 272).0.0080.63 Q value Q4 Defines the flow rate at point 4 on the PQ performance curve.See parameter 80.60 Q value Q1 (page 272).0.0080.64 Q value Q5 Defines the flow rate at point 5 on the PQ performance curve.See parameter 80.60 Q value Q1 (page 272).0.008181 Sensor settings Defines the sensor settings for inlet and outlet pressureprotection function.81.01 Actual inletpressureShows the actual inlet pressure.Note: By default the parameter unit will be bar. However, theunit can be changed according to the parameter 81.20Pressure unit.0.000.00...32767.00 bar Actual inlet pressure. 1 = 1 bar81.02 Actual outletpressureShows the actual outlet pressure. 0.000.00...32767.00 bar Actual outlet pressure. 1 = 1 bar81.10 Inlet pressuresourceSelects the primary source used for pump inlet pressuremeasurement.AI1 scaledNot selected None 0AI1 scaled Parameter 12.12 AI1 scaled value. 1AI2 scaled Parameter 12.22 AI2 scaled value. 2Freq in scaled Parameter 11.39 Freq in 1 scaled value. 3AI1 percent Parameter 12.101 AI1 percent value. 8AI2 percent Parameter 12.102 AI2 percent value. 9Feedback storage Parameter 40.91 Feedback data storage. 10Other [bit] Source selection (see Terms and abbreviations on page 100). -81.11 Outlet pressuresourceSelects the primary source used for pump outlet pressuremeasurement.AI2 scaledNot selected None 0AI1 scaled Parameter 12.12 AI1 scaled value. 1AI2 scaled Parameter 12.22 AI2 scaled value. 2Freq in scaled Parameter 11.39 Freq in 1 scaled value. 3AI1 percent Parameter 12.101 AI1 percent value. 8AI2 percent Parameter 12.102 AI2 percent value. 9Feedback storage Parameter 40.91 Feedback data storage. 10Other [bit] Source selection (see Terms and abbreviations on page 100). -81.12 Sensors heightdifferenceDefines the height difference between inlet and outletpressure sensors for flow calculation.0.000.00...32767.00 m Sensors height difference. 1 = 1 m81.20 Pressure unit Selects the unit of pressure. barbar Pressure 0No. Name/Value Description Def/FbEq16