178 Technical dataTerminal and lead-through data for the power cables IECInput, motor, resistor and DC cable lead-throughs, maximum wire sizes (per phase)and terminal screw sizes and tightening torques (T) are given below.FramesizeCable lead-throughsL1, L2, L3, T1/U, T2/V, T3/W terminals Grounding terminalsPercabletypeØ 1) Min wire size(solid/stranded) 3)Max wire size(solid/stranded)T Max wire size Tpcs mm mm2 mm 2 N·m mm 2 N·mR1 1 30 0.20/0.25 6/4 1.2…1.5 16/16 1.5R2 1 30 0.5/0.5 16/16 1.2…1.5 16/16 1.5R3 1 30 0.5/0.5 35/25 2.5…4.5 35/35 1.5R4 1 45 0.5/0.5 50 4.0 35/35 1.5R5 1 45 6 70 5.6 - 2) 1.5R6 1 45 25 150 30 - 2) 1.5R7 1 54 95 240 40 - 2) 1.5R8 2 45 2×50 2×150 40 - 2) 1.5R9 2 54 2×95 2×240 70 - 2) 1.53AXD00000586715.xls J1) Maximum cable diameter accepted. For the lead-through plate hole diameters, see chapter Dimensiondrawings on page 203.2) Either cable lug (R5, see page 109) or clamp (R6…R9, see page 113) is used for grounding.3) Note: Minimum wire size does not necessarily have enough current capability for full load. Make sure theinstallation complies with local laws and regulations.Note: For the tightening torques of the grounding terminals, see sections Connection procedure, framesR1…R4 on page 97, Connection procedure, frame R5 on page 105 and Connection procedure, framesR6…R9 on page 111.