186 Technical dataControl connection dataExternal power supply Maximum power:Frames R1…R5: 25 W, 1.04 A at 24 V AC/DC ±10%with an option moduleFrames R6…R9: 36 W, 1.50 A at 24 V AC/DC ±10% asstandardSupplied from an external power supply through optionmodule CMOD-01 or CMOD-02 with frames R1…R5. Withframes R6…R9 no options are needed.Terminal size:Frames R1…R5: 0.2…2.5 mm 2Frames R6…R9: 0.14…2.5 mm 2+24 V DC output(Term. 10)Total load capacity of this outputs is 6.0 W (250 mA / 24 V)minus the power taken by the option modules installed onthe board.Terminal size:Frames R1…R5: 0.2…2.5 mm 2Frames R6…R9: 0.14…2.5 mm 2Digital inputs DI1…DI6(Term. 13…18)Input type: NPN/PNPTerminal size:Frames R1…R5: 0.14…1.5 mm 2Frames R6…R9: 0.14…2.5 mm 2DI1…DI5 (Term.13…17)12/24 V DC logic levels: “0” < 4 V, “1” > 8 VRin : 3 kohmHardware filtering: 0.04 ms, digital filtering: 2 ms samplingDI5 (Term.17)Can be used as a digital or frequency input.12/24 V DC logic levels: “0” < 3 V, “1” > 8 VRin : 3 kohmMax. frequency 16 kHzSymmetrical signal (duty cycle D = 0.50)DI6 (Term. 18)Can be used as a digital or PTC input.Digital input mode12/24 V DC logic levels: “0” < 4 V, “1” > 8 VRin : 3 kohmHardware filtering: 0.04 ms, digital filtering: 2 ms samplingNote: DI6 is not supported in the NPN configuration.PTC mode – PTC thermistor can be connected betweenDI6 and +24VDC: < 1.5 kohm = ‘1’ (low temperature), >4 kohm = ‘0’ (high temperature), open circuit = ‘0’ (hightemperature).DI6 is not a reinforced/double insulated input. Connectingthe motor PTC sensor to this input requires usage of areinforced/double insulated PTC sensor inside the motor.