Maintenance 141 Start the drive following chapter of “Operation”Attention:• It is not allowed to start the drive if there is any condensing in drives. Make sure toheat and remove the condense and moisture in drives before drives are ready toSUPPLY ON.• Reform DC-link capacitors in Power modules and spare power modules If the stockage more than 1year following 2UBB017371_ACS580MV capacitor reforminginstruction.ABB provide standard drive startup service package. 400-810-88852 All power cables to drive, and from drive to motor are meggered, and measured values are withinthe required limits.Spare parts1 Sufficient number and correct type of spare parts available.2 For power modules, need to check their age. If stock age is more than 1year, the DC capacitorsneed to be reformed later.Power supply1 All auxiliary power supplies from external sources are switched on.2 All internal circuit breakers of the drive are closed.3 All grounding devices are removed.4 All covers are mounted and the doors are closed, locked and / or bolted.5 There is no run interlock active.6 MCB is in operating position.