Output power (energy storage) connectionACS880-1604LC-xxxxx-7 = Maximum output voltage 150 V…95% of UDC (DriveDC voltage in the DC bus). This is indicated in the type designation label as typicaloutput voltage range 50…668 / 764 / 878 V DC (764 V DC for UL/CSA).Recommended output voltage 150 V…80% of UDC.Voltage (U2)See section Ratings.CurrentSee the dimension drawings. Note that frame R8i module has a quick connector.Converter module outputterminals100 m (328 ft)Maximum energy storagecable lengthControl accuracy – Current and voltage controlperformance dataStep response time < 10 ms for a reference step 0% to 50% of the drive nominalcurrentCurrent control dynamicresponseCurrent error < 1% of the drive nominal current ratingFor the DC current ripple, see Ratings (page 126).Current control accuracy(static)Voltage error < 1% of the drive nominal voltage (converter with the optional BAMUvoltage/current measurement unit)Note:If the converter does not include the BAMU voltage/current measurement unit, thevoltage measurement accuracy depends on the customer's measurement device.Energy storage voltagecontrol accuracy (static)Control unit connection dataSee Control units of the drive.Coolant connectionsTube fitting, quick coupler for 16/13 mm polyamide (PA) pipe.Optical componentsThe specifications of the optic cable are as follows:• Storage temperature: -55 … +85 °C• Installation temperature: -20 … +70 °C• Maximum short-term tensile force: 50 N• Minimum short-term bend radius: 25 mm• Minimum long-term bend radius: 35 mm• Maximum long-term tensile load: 1 N• Flexing: Max. 1000 cyclesABB drive products in general utilize 5 and 10 MBd (megabaud) optical components fromAvago Technologies’ Versatile Link range. Note that the optical component type is notdirectly related to the actual communication speed.Technical data 133