Parameters 16112.27 AI2 min Defines the minimum site value for analog input AI2.Set the value actually sent to the drive when the analog signalfrom plant is wound to its minimum setting.See also parameter 12.01 AI tune.0.000 mA orV-22.000 … 22.000mA or VMinimum value of AI2. 1000 = 1 mAor V12.28 AI2 max Defines the maximum site value for analog input AI2.Set the value actually sent to the drive when the analog signalfrom plant is wound to its maximum setting.See also parameter 12.01 AI tune.20.000 mA or10.000 V-22.000 … 22.000mA or VMaximum value of AI2. 1000 = 1 mAor V12.29 AI2 scaled at AI2minDefines the real value that corresponds to the minimumanalog input AI2 value defined by parameter 12.27 AI2 min.(Changing the polarity settings of 12.29 and 12.30 caneffectively invert the analog input.)0.000-32768.000 …32767.000Real value corresponding to minimum AI2 value. 1 = 112.30 AI2 scaled at AI2maxDefines the real value that corresponds to the maximumanalog input AI2 value defined by parameter 12.28 AI2 max.See the drawing at parameter 12.29 AI2 scaled at AI2 min.100.000-32768.000 …32767.000Real value corresponding to maximum AI2 value. 1 = 11313 Standard AO Configuration of standard analog outputs.13.11 AO1 actual value Displays the value of AO1 in mA.This parameter is read-only.-0.000 … 22.000 mA Value of AO1. 1000 = 1 mA13.12 AO1 source Selects a signal to be connected to analog output AO1.Alternatively, sets the output to excitation mode to feed aconstant current to a temperature sensor.Motor speedusedZero None. 0Motor speed used 01.01 Motor speed used (page 115). 1Output frequency 01.06 Output frequency (page 115). 3Motor current 01.07 Motor current (page 115). 4No. Name/Value Description Def/FbEq1612.3012.2812.2712.29AIin (12.21)AIscaled (12.22)ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de