Parameters 20320.27 Jogging 2 startsourceIf enabled by parameter 20.25 Jogging enable, selects thesource for the activation of jogging function 2. (Joggingfunction 2 can also be activated through fieldbus regardless ofparameter 20.25.)1 = Jogging 2 active.For the selections, see parameter 20.26 Jogging 1 startsource.Note: If both jogging 1 and 2 are activated, the one that wasactivated first has priority.Not selected20.29 Local start triggertypeDefines whether the start signal for local control (for example,control panel or PC tool) is edge-triggered or level-triggered.EdgeEdge The start signal is edge-triggered. 0Level The start signal is level-triggered. 120.30 Enable signalswarning functionSelects enable signal (eg. run enable, start enable) warningsto be suppressed. This parameter can be used to preventthese warnings from flooding the event log.Whenever a bit of this parameter is set to 1, the correspondingwarning is suppressed, ie. no warning is generated even if thesignal is switched off.The bits of this binary number correspond to the followingwarnings:00b00b…11b Suppression of “enable signal missing” warnings. 1 = 12121 Start/stop mode Start and stop modes; emergency stop mode and signalsource selection; DC magnetization settings; autophasingmode selection.21.01 Start mode Selects the motor start function for the DTC motor controlmode, ie. when 99.04 Motor control mode is set to DTC.Notes:• The start function for the scalar motor control mode isselected by parameter 21.19 Scalar start mode.• Starting into a rotating motor is not possible when DCmagnetizing is selected (Fast or Constant time).• With permanent magnet motors and synchronousreluctance motors, Automatic start mode must be used.• This parameter cannot be changed while the drive isrunning.See also section DC magnetization (page 63).AutomaticFast The drive pre-magnetizes the motor before start. The pre-magnetizing time is determined automatically, being typically200 ms to 2 s depending on motor size. This mode should beselected if a high break-away torque is required.0No. Name/Value Description Def/FbEq16Bit Name Warning0 Enable Start AFEA Enable start signal missing1 Run enable 1 AFEB Run enable missing2…15 Reservedghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de