Parameters 2552929 Voltage referencechainSettings for the DC voltage reference chain.See section DC voltage control mode (page 23) and thecontrol chain diagrams (pages 588 and 589).This group is only visible with a BCU control unit.29.01 Torque ref DCvoltage controlDisplays the DC voltage controller output that is transferred tothe torque controller.This parameter is read-only.--1600.0 … 1600.0% Final DC voltage reference. 1 = 1%29.02 DC voltage ref Displays the DC voltage reference after the function appliedby parameter 29.13 DC voltage ref1 function (if any), and afterselection (29.14 DC voltage ref1/2 selection). See the diagramat parameter 29.11 DC voltage ref1 source.-0…2000 V DC voltage reference after selection. 10 = 1 V29.03 DC voltage ref used Displays the DC voltage reference betweenminimum/maximum limitation and ramping.-0…2000 V DC voltage reference before ramping. 10 = 1 V29.04 DC voltage reframpedDisplays the DC voltage reference after ramping. -0…2000 V DC voltage reference after ramping. 10 = 1 V29.05 Filtered DC voltage Displays the measured DC voltage after filtering. -0…2000 V Measured and filtered DC voltage. 10 = 1 V29.06 DC voltage error Displays the difference between the ramped voltage reference(29.04) and measured, filtered DC voltage (29.05).--2000…2000 V Measured and filtered DC voltage. 10 = 1 V29.07 Power reference Displays the output of the PI controller, ie. the DC voltagereference before it is converted to a torque reference.--300.00 … 300.00% Output of the PI controller. 10 = 1%29.09 Minimum DCvoltage referenceDefines a minimum limit for the DC voltage reference before itis ramped.0 V0…2000 V Minimum DC voltage reference. 1 = 1 V29.10 Maximum DCvoltage referenceDefines a maximum limit for the DC voltage reference before itis ramped.2000 V0…2000 V Maximum DC voltage reference. 1 = 1 VNo. Name/Value Description Def/FbEq16ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de