Table 31: General settings parameters for the Measurement functionSetting Short description SelectedvalueCommentOperation OperationOff/OnOn Function must beOnPowAmpFact Amplitude factor to scalepower calculations1.000 Typically no scaling is requiredPowAngComp Angle compensation for phaseshift between measured I & U180.0 Typically no angle compensation is required.However here the required direction of P & Qmeasurement is towards busbar (Not per IEDinternal default direction). Therefore anglecompensation have to be used in order to getmeasurements in aliment with the requireddirection.Mode Selection of measured currentand voltageL1L2 Only UL1L2 phase-to-phase voltage isavailablek Low pass filter coefficient forpower measurement, U and I0.00 Typically no additional filtering is requiredUGenZeroDb Zero point clamping in % ofUbase25 Set minimum voltage level to 25%IGenZeroDb Zero point clamping in % ofIbase3 Set minimum current level to 3%UBase (set inGlobal base)Base setting for voltage levelin kV35.00 Set LV side rated phase-to-phase voltageIBase (set inGlobal base)Base setting for current levelin A495 Set transformer LV winding rated current13.2 Gas medium supervision SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v313.2.1 IdentificationGUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGas medium supervision SSIMG - 6313.2.2 Application GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5Gas medium supervision (SSIMG) is used for monitoring the circuit breaker condition. Properarc extinction by the compressed gas in the circuit breaker is very important. When thepressure becomes too low compared to the required value, the circuit breaker operation shallbe blocked to minimize the risk of internal failure. Binary information based on the gaspressure in the circuit breaker is used as an input signal to the function. The functiongenerates alarms based on the received information.13.2.3 Setting guidelines GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v1The parameters for the gas medium supervision SSIMG are set via the local HMI or PCM600.•Operation:Off/On•PresAlmLimit: Alarm setting pressure limit for gas medium supervision•PresLOLimit: Pressure lockout setting limit for gas medium supervision•TempAlarmLimit: Temperature alarm level setting of the gas medium1MRK 504 158-UEN A Section 13Monitoring207Application manual