15.2.2 Horizontal communication via GOOSE for interlockingGOOSEINTLKRCV SEMOD173197-1 v2PID-415-SETTINGS v5Table 32: GOOSEINTLKRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On15.2.3 Setting guidelines SEMOD55317-5 v6There are two settings related to the IEC 61850–8–1 protocol:Operation User can set IEC 61850 communication toOn orOff.GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send and received.15.2.4 Generic communication function for Single Point indicationSPGAPC, SP16GAPC SEMOD55999-1 v415.2.4.1 Application SEMOD55350-5 v7Generic communication function for Single Point Value (SPGAPC) function is used to send onesingle logical output to other systems or equipment in the substation. It has one visible input,that should be connected in ACT tool.15.2.4.2 Setting guidelines SEMOD55376-5 v5There are no settings available for the user for SPGAPC.15.2.5 Generic communication function for Measured Value MVGAPCSEMOD55402-1 v315.2.5.1 Application SEMOD55872-5 v9Generic communication function for Measured Value MVGAPC function is used to send theinstantaneous value of an analog signal to other systems or equipment in the substation. Itcan also be used inside the same IED, to attach a RANGE aspect to an analog value and topermit measurement supervision on that value.15.2.5.2 Setting guidelines SEMOD55424-5 v5The settings available for Generic communication function for Measured Value (MVGAPC)function allows the user to choose a deadband and a zero deadband for the monitored signal.Values within the zero deadband are considered as zero.The high and low limit settings provides limits for the high-high-, high, normal, low and low-low ranges of the measured value. The actual range of the measured value is shown on therange output of MVGAPC function block. When a Measured value expander block (RANGE_XP)1MRK 504 158-UEN A Section 15Station communication229Application manual