Name Type Default DescriptionI3PDIR GROUPSIGNAL- Group connection for directional currentBLOCK BOOLEAN 0 General blockBLKTR BOOLEAN 0 Block of tripBLK1 BOOLEAN 0 Block of step 1 (Pickup and trip)BLK2 BOOLEAN 0 Block of step 2 (Pickup and trip)BLK3 BOOLEAN 0 Block of step 3 (Pickup and trip)BLK4 BOOLEAN 0 Block of step 4 (Pickup and trip)MULTPU1 BOOLEAN 0 When activated, the pickup multiplier is in use for step1MULTPU2 BOOLEAN 0 When activated, the pickup multiplier is in use for step2MULTPU3 BOOLEAN 0 When activated, the pickup multiplier is in use for step3MULTPU4 BOOLEAN 0 When activated, the pickup multiplier is in use for step452a BOOLEAN 0 Breaker positionCLOSECMD BOOLEAN 0 Breaker close commandOPENCMD BOOLEAN 0 Breaker open commandTable 100:EF4PTOC (51N_67N) Output signalsName Type DescriptionTRIP BOOLEAN General trip signalTRST1 BOOLEAN Trip signal from step 1TRST2 BOOLEAN Trip signal from step 2TRST3 BOOLEAN Trip signal from step 3TRST4 BOOLEAN Trip signal from step 4TRSOTF BOOLEAN Trip signal from switch onto fault functionPICKUP BOOLEAN Common pickup signalPUST1 BOOLEAN Pickup signal step 1PUST2 BOOLEAN Pickup signal step 2PUST3 BOOLEAN Pickup signal step 3PUST4 BOOLEAN Pickup signal step 4PUSOTF BOOLEAN Pickup signal from switch onto fault functionPUFW BOOLEAN Pick up foward directionPUREV BOOLEAN Pick up reverse direction2NDHARMD BOOLEAN 2nd harmonic block signal8.2.5 SettingsSection 8 1MRK 511 365-UUS ACurrent protection190 Phasor measurement unit RES670 2.1 ANSITechnical manual