18.7.5.4 SignalsTable 513:I103EF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting51_EFFW BOOLEAN 0 Information number 51, ground-fault forward52_EFREV BOOLEAN 0 Information number 52, ground-fault reverse18.7.5.5 SettingsTable 514:I103EF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 160 Function type (1-255)18.7.6 Function status fault protection for IEC 60870-5-103I103FLTPROT18.7.6.1 FunctionalityI103FLTPROT is used for fault indications in monitor direction. Each input on thefunction block is specific for a certain fault type and therefore must be connected to acorrespondent signal present in the configuration. For example: 68_TRGEN representsthe General Trip of the device, and therefore must be connected to the general trip signalSMPPTRC_TRIP or equivalent.The delay observed in the protocol is the time difference in between the signal that istriggering the Disturbance Recorder and the respective configured signal to the IEC60870-5-103 I103FLTPROT.18.7.6.2 IdentificationFunction description Function blocknameIEC 60617identificationANSI/IEEE C37.2device numberFunction status fault protection for IEC60870-5-103I103FLTPROT - -1MRK 511 365-UUS A Section 18Station communicationPhasor measurement unit RES670 2.1 ANSI 647Technical manual