Name Values (Range) Unit Step Default DescriptionContTrCorr -0.010 - 0.010 s 0.001 0.005 Correction for time difference in auxiliary andmain contacts open timeOperTimeDelay 0.000 - 0.200 s 0.001 0.020 Time delay between change of status of tripoutput and start of main contact separationtDGasPresAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarmtDGasPresLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockoutInitCounterVal 0 - 9999 - 1 0 Initial value for number of operationsInitAccCurrPwr 0.00 - 9999.99 - 0.01 0.00 Initial value for accum I^CurrExponent integrover CB open travel time valueInitInactDays 0 - 9999 Day 1 0 Initial value for inactive daysInactiveAlHrs 0 - 23 Hour 1 0 Alarm time for inactive days counter in hours16.4.6 Monitored dataTable 425:SSCBR Monitored dataName Type Values (Range) Unit DescriptionTTRVOP REAL - ms Travel time of the CB duringopening operationTTRVCL REAL - ms Travel time of the CB duringclosing operationNOOPER INTEGER - - Number of CB operation cycleCBLIFEPH INTEGER - - CB Remaining life ofrespective phaseINADAYS INTEGER - - The number of days CB hasbeen inactiveIPOWPH REAL - - Accumulated I^CurrExponentintegrated over CB open traveltimeSPCHT REAL - s The charging time of the CBspring16.4.7 Operation principleThe breaker monitoring function includes metering and monitoring subfunctions. Thesubfunctions can be enabled and disabled with the Operation setting. The correspondingparameter values are Enabled and Disabled.The operation of the subfunctions is described by the module diagram as shown in Figure196. All the modules in the diagram are explained in subsequent sections.Section 16 1MRK 511 365-UUS AMonitoring528 Phasor measurement unit RES670 2.1 ANSITechnical manual