Name Type Default DescriptionIN10 BOOLEAN 0 Input 10IN11 BOOLEAN 0 Input 11IN12 BOOLEAN 0 Input 12IN13 BOOLEAN 0 Input 13IN14 BOOLEAN 0 Input 14IN15 BOOLEAN 0 Input 15IN16 BOOLEAN 0 Input 16Table 353:BTIGAPC Output signalsName Type DescriptionOUT INTEGER Output value15.11.5 SettingsThe function does not have any parameters available in the local HMI or PCM600.15.11.6 Monitored dataTable 354:BTIGAPC Monitored dataName Type Values (Range) Unit DescriptionOUT INTEGER - - Output value15.11.7 Operation principleThe Boolean 16 to integer conversion with logic node representation function(BTIGAPC) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, toan integer. Each INx represents a value according to the table below from 0 to 32768. Thisfollows the general formula: INx = 2x-1 where 1≤x≤16. The sum of all the values on theactivated INx will be available on the output OUT as a sum of the integer values of all theinputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) areactivated, that is = Boolean 1, it corresponds to that integer 65535 is available on theoutput OUT. The BTIGAPC function is designed for receiving the integer input from astation computer - for example, over IEC 61850. If the BLOCK input is activated, it willfreeze the logical outputs at the last value.Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.1MRK 511 365-UUS A Section 15LogicPhasor measurement unit RES670 2.1 ANSI 463Technical manual