11.1.4 SettingsTable 187:CVGAPC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disabled/EnabledCurrentInput Phase APhase BPhase CPosSeqNegSeq3*ZeroSeqMaxPhMinPhUnbalancePhPhase ABPhase BCPhase CAMaxPh-PhMinPh-PhUnbalancePh-Ph- - MaxPh Select current signal which will be measuredinside functionVoltageInput Phase APhase BPhase CPosSeq-NegSeq-3*ZeroSeqMaxPhMinPhUnbalancePhPhase ABPhase BCPhase CAMaxPh-PhMinPh-PhUnbalancePh-Ph- - MaxPh Select voltage signal which will be measuredinside functionOperHarmRestr DisabledEnabled- - Disabled Disable/Enable operation of 2nd harmonicrestrainl_2nd/l_fund 10.0 - 50.0 % 1.0 20.0 Ratio of second to fundamental currentharmonic in %BlkLevel2nd 10 - 5000 %IB 1 5000 Harm analyse disabled above this current levelin % of fundamental currentEnRestrainCurr DisabledEnabled- - Disabled Disable/Enable current restrain functionRestrCurrInput PosSeqNegSeq3*ZeroSeqMax- - PosSeq Select current signal which will be used forcurrent restrainRestrCurrCoeff 0.00 - 5.00 - 0.01 0.00 Restraining current coefficientRCADir -180 - 180 Deg 1 -75 Relay Characteristic AngleROADir 1 - 90 Deg 1 75 Relay Operate AngleTable continues on next pageSection 11 1MRK 511 365-UUS AMultipurpose protection324 Phasor measurement unit RES670 2.1 ANSITechnical manual